CS88 Energy Code Feasibility Study in Amesbury, Massachusetts

Energy code feasibility study for a 83-unit Townhomes in Massachusetts. Compares multiple design paths. Recommended: NEXTGEN (All-Electric). View full study.

Study Type
Energy Code Feasibility Study
State
Massachusetts
Units
83
Building Type
Townhomes
Fuel Type
All-Electric
Recommended Path
NEXTGEN (All-Electric)

Goal

To find the most cost-effective compliance path, this report isolates energy code related costs from total construction. We use real bid data from vendors & clients to create a reliable framework for aligning incentives and design, with all recommendations confirmed by detailed energy modeling.

Project

  • Amesbury, MA 01913
  • 37 Buildings | 83 Units | 177,740 SF Conditioned
  • New Construction | 3-story 1-unit townhome (x11), 3-story 2-unit townhome (x10), 3-story 3-unit townhome (x12), 3-story 4-unit townhome (x4)
  • All-Electric OR Mixed Fuel | 2021 IECC with MA Amendments (Stretch Code) | HERS ≤ 45 (All-Electric) OR HERS ≤ 42 (Mixed Fuel) | ENERGY STAR SFNH v3.2 (optional) | ENERGY STAR NextGen (optional)

Overview

Read This: This report compares different ways you can build the project and meet energy code, looking at both cost and incentives, with the ultimate goal as finding the most affordable path.

  • The overview outlines the key differences between each of the paths we show in this report and why we recommend the one we picked over the others.
  • The recommended design section is where we share the requirements and incentives for the path we think is best based on affordability.
  • The path comparison section shows the detailed requirements and incentives for each path we compared, basically showing our work if you want to dig in.

Product Recs: All product recommendations are recommendations only and can be substituted with any equivalent or better match.

Path Summaries

All three paths meet Massachusetts energy code and are modeled to pass on a lean margin, so the choice between them is a matter of cost and constructability rather than compliance.

NEXTGEN (All-Electric): Recommended

This is the least expensive path at approximately $35.39/sf net, and the air barrier sits on the sheathing. It keeps the project fully electric, which preserves the $1,245,000 Mass Save ENERGY STAR single-family townhome incentive ($15,000 per home) and aligns with the direction Massachusetts energy code is heading. For this project, this is the right choice.

HERS40-ELECTRIC (All-Electric): Alternative

At approximately $39.54/sf net, about $4/sf more than the NEXTGEN path, this path stays all-electric and adds $20,750 in incentives, which does not close the cost gap. The two all-electric paths build in much the same way, so the premium buys a deeper margin under the code ceiling. Choose this path when that margin matters more than first cost.

HERS40-GAS (Mixed-Fuel): Not Recommended

This is the most expensive path at approximately $48.84/sf net, about $13/sf more than the NEXTGEN path, and it is the most labor-intensive to build. Mixed-fuel construction forfeits the $1,245,000 Mass Save ENERGY STAR single-family townhome incentive and runs against the direction Massachusetts energy code is heading. The only reason to choose this path is a market that specifically demands gas service.

What Changes Between Paths

Item

HERS40-GAS

HERS40-ELECTRIC

NEXTGEN (Recommended)

Exterior Walls

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-10 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-10 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-9 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

Roof

Vented attic: ≥ R-60 insulation.

Vented attic: ≥ R-60 insulation.

Vented attic: ≥ R-49 insulation.

Windows & Glass Doors

High performance, U ≤ 0.18 / SHGC ≤ 0.18.

High performance, U ≤ 0.18 / SHGC ≤ 0.18.

High performance, U ≤ 0.25 / SHGC ≤ 0.25.

HVAC

Natural gas boiler (as modeled); AFUE ≥ 96; cooling by a separate system, cooling only; SEER2 ≥ 15.2. See HVAC Design Loads.

Ducted air-source heat pump (as modeled); SEER2 ≥ 17.5; HSPF2 ≥ 10.5. See HVAC Design Loads.

Ducted air-source heat pump (as modeled); SEER2 ≥ 17.5; HSPF2 ≥ 10.5; 5 kW electric heat kit on every four-bedroom unit. See HVAC Design Loads.

DHW

Gas tankless water heater (as modeled); UEF ≥ 0.96.

3-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 4; 65 gal
4-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 4; 80 gal

3-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 3.5; 65 gal
4-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 3.5; 80 gal

Clothes Dryer

Standard electric dryer; vented; CEF ≥ 3.93.

Heat pump dryer; ventless; CEF ≥ 8.5.

Standard electric dryer; vented; CEF ≥ 3.93.

Stove / Oven

Electric range.

Electric induction cooktop; convection oven.

Electric range.

Cost $/sf

$48.47

$46.19

$42.02

Incentive $/sf

$0.00

$7.12

$7.00

Net $/sf

$48.84

$39.54

$35.39

Single Family OR Low Rise Buildings (Stretch)

Single Family OR Low Rise Buildings (Stretch)

Code Path

  • HERS: Amesbury Stretch. Three-story dwellings under 225 CMR 22. The all-electric Stretch ceiling is HERS ≤ 45 and the mixed-fuel Stretch ceiling is HERS ≤ 42 (225 CMR 22 Table R406.5).

Permit Requirements

  • HERS: Proposed HERS/ERI compliance documentation for each dwelling unit type (rated Index, software name/version, modeling inputs) and component specifications on the drawings, with the building permit application (225 CMR 22 R406).

Certificate of Occupancy Requirements

  • HERS: Confirmed as-built HERS certificates; dwelling-unit air-leakage testing (and duct / ventilation verification where required) per the adopted testing rules and ANSI/RESNET/ICC 380 methods, with sampling as allowed for multifamily.

Recommended Design

This section outlines the design requirements, product recommendations, and incentives for the design that we believe will be the most affordable path to meeting energy code.

Recommended Design - Incentives

Incentives Available: $1,245,000

  • MassSave Single-Family ENERGY STAR NextGen Tier ($1,245,000) (Program Breakdown): You get this rebate for building a home that meets MassSave's ENERGY STAR NextGen tier. The 2026 program terms require all-electric space conditioning, water heating, cooking and clothes drying; a HERS Index of 45 or lower, or at least 30 percent savings over the Massachusetts User Defined Reference Home; air leakage of 1.5 ACH50 or lower, tested by an approved HERS rating company; balanced ventilation through an ERV or HRV; an EV-ready parking space built to 225 CMR 22 section R404.4; and certification by a program-approved HERS rating company to ENERGY STAR Single-Family New Homes v3.2 (or Multifamily New Construction v1.2) and to ENERGY STAR NextGen. Testing and certification typically happen at the end of construction, around when the certificate of occupancy is received. This rebate comes in the form of a check within 4 months of the certification paperwork being provided to MassSave.

HVAC Design Loads

Essex County, MA · heating 1.0°F/70.0°F · cooling 90.0°F/75.0°F · all values kBtuh · 5 kW backup heat kit on some unit types

Design heat loss · components

Unit type

Walls & rim joists

Roof / ceiling

Slab, floors & below grade

Windows & doors

Infiltration

Ventilation

Design heat loss

Design heat loss at selection

3-Bedroom

6.3

3.0

5.8

9.9

3.8

3.3

32.2 @ 1°F

32.2 @ 1°F

4-Bedroom

10.7

2.4

13.1

8.9

3.9

3.9

43.1 @ 1°F

43.1 @ 1°F

Design heat gain · components

Unit type

Solar through glazing

Envelope conduction

Internal gains

Infiltration & ventilation

Latent

Total heat gain

Sensible heat ratio

3-Bedroom

4.7

4.4

2.5

2.6

4.1

18.4

0.78

4-Bedroom

4.9

5.8

2.8

3.0

4.7

21.2

0.78

Selection

Unit type

Cooling Capacity

Minimum Heating Capacity

3-Bedroom

16.6 to 23.9 kBtuh rated

≥ 32.2 kBtuh @ 1°F

4-Bedroom

19.1 to 27.6 kBtuh rated

≥ 43.1 kBtuh @ 1°F

Heating coverage at 1°F

Unit type

Recommended unit

Heat pump output at 1°F

5 kW heat kit at 208 V (3.76 kW delivered)

Total heat at 1°F

Coverage

3-Bedroom

42 kBtuh nominal

37.0 kBtuh

Not on every unit

37.0 kBtuh

Pass by 4.8 kBtuh

4-Bedroom

48 kBtuh nominal

42.2 kBtuh

12.8 kBtuh

55.0 kBtuh

Pass by 11.9 kBtuh

ENERGY STAR Total UA

Item

Detail

Climate zone

IECC 5A (2021 IECC map, Footnote 6)

Program

ENERGY STAR Single-Family New Homes National v3.2 (Rev. 14)

Rule

Design Review Item 2.1: proposed total UA ≤ 100% of the UA from 2021 IECC Table R402.1.2 U-factors on the same areas (Footnote 7)

Code reference

National Rater Design Review Checklist Rev. 14, Item 2.1 with Footnotes 6 to 8; 2021 IECC Table R402.1.2 and Section R402.1.5

Areas and U-factors

Energy model, per home: walls net of windows and doors, rim joists as above-grade wall

Openings

Opaque doors use the fenestration U-factor. Footnote 8a/8b exemptions not needed: every window and door meets U-0.30

Fenestration

Area-weighted window and door U 0.25, limit 0.48 (R402.5); no SHGC limit in CZ 5A (Table R402.1.2 NR; Item 2.2 covers CZ 1-3, 4A and 4B only)

Assembly

Proposed spec

Walls

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-9 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

Rim joists

≥ R-21 rim/band insulation at floor transitions.

Roof

Vented attic: ≥ R-49 insulation.

Slab

≥ R-20 perimeter insulation, 2 ft deep, at the interior face of the slab edge, plus ≥ R-20 under-slab insulation, 2 ft wide; provides a full thermal break.

Windows

High performance, U ≤ 0.25 / SHGC ≤ 0.25.

Doors

Opaque door, U ≤ 0.20 (R-5.0).

Component UA

Component

Area

Proposed U or F

Proposed UA

Reference U or F

Reference UA

Above-grade walls (net of openings)

10,702 sf

0.0394

421.8

0.045

481.6

Rim joists

1,163 sf

0.0476

55.4

0.045

52.3

Ceilings

6,850 sf

0.0243

166.5

0.024

164.4

Floors over unconditioned

500 sf

0.0357

17.9

0.033

16.5

Slab-on-grade edge (F x perimeter)

555 lf

0.5100

283.0

0.480

266.3

Windows

2,428 sf

0.2500

607.0

0.300

728.4

Opaque doors

120 sf

0.2000

24.0

0.300

36.0

Total

1,575.5

1,745.5

Total UA

Home

Proposed UA

Reference UA

% of reference

Result

3 BR, 2,100 sf

255.2

282.6

90.3%

PASS

4 BR, 2,000 sf

224.5

250.7

89.5%

PASS

3 BR, 2,160 sf

255.9

283.3

90.3%

PASS

3 BR, 2,440 sf

313.0

346.8

90.3%

PASS

4 BR, 2,500 sf

386.6

425.5

90.9%

PASS

3 BR, 1,800 sf

140.2

156.6

89.5%

PASS

Result

1,575.5

1,745.5

90.3%

PASS

Recommended Design - Units

Item

Detailed Specifications

Exterior Walls

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-9 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.). (Product Rec).

Below Grade Walls

N/A

Corridor Walls

N/A

Slab

≥ R-20 perimeter insulation, 2 ft deep, at the interior face of the slab edge, plus ≥ R-20 under-slab insulation, 2 ft wide; provides a full thermal break.

Floor Over Unconditioned Space

N/A

Floor Over Garage

≥ R-30 cavity insulation.

Floor Over Podium

N/A

Rim Joists

≥ R-21 rim/band insulation at floor transitions.

Roof

Vented attic: ≥ R-49 insulation.

Windows & Glass Doors

High performance, U ≤ 0.25 / SHGC ≤ 0.25. (Product Rec).

Doors

Opaque door, U ≤ 0.20 (R-5.0).

Air Sealing

≤ 1.5 ACH50; tested. (Air Sealing Protocol)

HVAC

Ducted air-source heat pump (as modeled); SEER2 ≥ 17.5; HSPF2 ≥ 10.5; 5 kW electric heat kit on every four-bedroom unit. See HVAC Design Loads. (Product Rec).

Ductwork

Supply and return ducts in attic under insulation poorly vented insulated to code minimum; ducts in conditioned space insulated to code minimum.

Duct Sealing

≤ greater of 40 CFM25 or 4 CFM25 per 100 sqft of conditioned floor area; tested at rough-in, after the HVAC is installed. (Duct Sealing Protocol)

HVAC Grading

Fan Flow Test: Grade I
Watt Draw Test: Grade I
Refrigerant Charge: Grade I
HVAC installer must provide photo of the digital refrigerant scale showing the amount charged, with the tank on the scale and hoses connected to the outdoor unit, along with a photo of the outdoor unit's data plate.

Mechanical Ventilation

In-unit ERV (Product Rec).
3-bedroom: 110 CFM, ≥ 81% ASRE
4-bedroom: 130 CFM, ≥ 79% ASRE

Local Mechanical Exhaust

Bathroom(s): at least 50 CFM intermittent and up to 3.0 sones, or at least 20 CFM continuous and up to 2.0 sones.
Kitchen(s): at least 100 CFM intermittent and up to 3.0 sones, or continuous at 5 ACH.
Both: exhaust directly outdoors with ENERGY STAR certified fans. A balanced ERV or HRV serving the space may satisfy this requirement.

Thermostats

Programmable thermostat (as modeled).

DHW

3-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 3.5; 65 gal (Product Rec).
4-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 3.5; 80 gal

DHW Piping

Supply piping insulated to ≥ R-3.

Water Fixtures

WaterSense certified (Lavatory ≤ 1.2 GPM; Shower ≤ 2.0 GPM; Kitchen ≤ 2.2 GPM).

Refrigerator

≤ 600 kWh/yr; electric. (Product Rec).

Dishwasher

≤ 240 kWh/yr; electric. (Product Rec).

Clothes Washer

IMEF ≥ 2.06; IWF ≤ 4.2; ≤ 152 kWh/yr; electric. (Product Rec).

Clothes Dryer

Standard electric dryer; vented; CEF ≥ 3.93. (Product Rec).

Stove / Oven

Electric range. (Product Rec).

Lighting

≥ 100% high-efficacy (LED).

Solar Ready

Reserve an unobstructed rooftop solar-ready zone (at least 300 sq ft; 150 sq ft for small townhouses) with structural capacity, a conduit pathway, and reserved electrical-panel space. Waived if solar is already installed or the roof is heavily shaded.

EV Ready

One 50-amp Level II EV-ready circuit per dwelling unit.

HPWH Ready

N/A

Paperwork & Modeling

ENERGY STAR energy model to the ERI target, the ENERGY STAR design-review checklist, and an HVAC design report. Plus ENERGY STAR NextGen documentation: all-electric equipment and EV-charging provisions.

Testing & Verification

ENERGY STAR field verification: pre-drywall and final inspections, blower-door and duct-leakage tests, ventilation airflow, and HVAC installation grading. Plus ENERGY STAR NextGen verification: all-electric equipment and EV-charging infrastructure.

Recommended Design - Common Areas

Item

Common Areas (Residential Building)

Assembly Moisture Check

This section shows which air and vapor barriers are needed, and why.

Inputs

Item

Value

Climate zone

5A

Indoor air

70 F, 35% RH

Dewpoint of that indoor air

41 F

Outdoor air

1 F

Code

2018 IRC Table R702.7.1

Exterior Walls

#

Layer (inside to outside)

R

Running R

Temp

Dewpoint target

Vs dewpoint

1

Drywall

1.13

1.13

67.6 F

41 F

OK

2

Class II vapor retarder

0.00

1.13

67.6 F

41 F

OK

3

R-21 cavity insulation with 2x6 wood studs

21.00

22.13

22.2 F

41 F

First below dewpoint

4

Wood sheathing

0.62

22.75

20.8 F

41 F

Below dewpoint

5

Air barrier

0.00

22.75

20.8 F

41 F

Below dewpoint

6

R-9 continuous insulation

9.00

31.75

1.4 F

41 F

Below dewpoint

7

Siding / cladding

0.17

31.92

1.0 F

41 F

Below dewpoint

Conclusion: Layer 3 is the first row below dewpoint. It is the cold plane we protect. Indoor moisture can turn to water if it gets there, and can eventually cause mold. It can get there two ways. It gets there through the drywall, which is why the vapor retarder is on the inside of the wall. It also gets there through holes (outlets, gaps, plates), which is why the air barrier is on the sheathing. Same at the rim. Keep the R-9 going over the band.

Slab

#

Layer (inside to outside)

R

Running R

Temp

Dewpoint target

Vs dewpoint

1

Concrete slab

0.50

0.50

69.5 F

41 F

OK

2

Vapor retarder

0.00

0.50

69.5 F

41 F

OK

3

R-20 under slab and at the interior edge

20.00

20.50

50.0 F

41 F

OK

4

Gravel / ground

0.00

20.50

50.0 F

41 F

OK

Conclusion: No row drops below dewpoint. This is not the wall problem. Indoor air is not leaking to a cold sheathing. The vapor retarder is under the slab to stop moisture coming up from the ground. The slab itself is the air barrier.

Floor Over Garage

#

Layer (inside to outside)

R

Running R

Temp

Dewpoint target

Vs dewpoint

1

Floor finish

1.13

1.13

67.5 F

41 F

OK

2

R-30 cavity insulation

30.00

31.13

1.4 F

41 F

First below dewpoint

3

Air barrier

0.00

31.13

1.4 F

41 F

Below dewpoint

4

Garage

0.17

31.30

1.0 F

41 F

Below dewpoint

Conclusion: Layer 2 is the first row below dewpoint. It is the cold plane we protect. Indoor moisture can turn to water if it gets there, and can eventually cause mold. It can get there through holes, which is why the air barrier is at the insulated plane, not a drop-in ceiling.

Roof (vented attic)

#

Layer (inside to outside)

R

Running R

Temp

Dewpoint target

Vs dewpoint

1

Drywall ceiling

1.13

1.13

68.4 F

41 F

OK

2

Air barrier

0.00

1.13

68.4 F

41 F

OK

3

R-49 attic floor insulation

49.00

50.13

1.2 F

41 F

First below dewpoint

4

Vented attic

0.17

50.30

1.0 F

41 F

Below dewpoint

Conclusion: Layer 3 is the first row below dewpoint. It is the cold plane we protect. Indoor moisture can turn to water if it gets there, and can eventually cause mold. It can get there through holes (hatches, lights, plumbing), which is why the air barrier is on the ceiling, not the roof deck.

Exterior Walls (Recommended Design)

Exterior Walls (Recommended Design)

Slab (Recommended Design)

Slab (Recommended Design)

Floor Over Garage (Recommended Design)

Floor Over Garage (Recommended Design)

Rim Joists (Recommended Design)

Rim Joists (Recommended Design)

Roof (Recommended Design)

Roof (Recommended Design)

Path Comparison

This section shows the detailed requirements and incentives for each path we compared, basically showing our work of how we determined the recommended path is the most affordable way of meeting energy code compliance.

Path Comparison - Incentives

NEXTGEN: $1,245,000

  • MassSave Single-Family ENERGY STAR NextGen Tier ($1,245,000) (Program Breakdown): You get this rebate for building a home that meets MassSave's ENERGY STAR NextGen tier. The 2026 program terms require all-electric space conditioning, water heating, cooking and clothes drying; a HERS Index of 45 or lower, or at least 30 percent savings over the Massachusetts User Defined Reference Home; air leakage of 1.5 ACH50 or lower, tested by an approved HERS rating company; balanced ventilation through an ERV or HRV; an EV-ready parking space built to 225 CMR 22 section R404.4; and certification by a program-approved HERS rating company to ENERGY STAR Single-Family New Homes v3.2 (or Multifamily New Construction v1.2) and to ENERGY STAR NextGen. Testing and certification typically happen at the end of construction, around when the certificate of occupancy is received. This rebate comes in the form of a check within 4 months of the certification paperwork being provided to MassSave.

HERS40-ELECTRIC: $1,265,750

  • MassSave Single-Family ENERGY STAR NextGen Tier ($1,245,000) (Program Breakdown): You get this rebate for building a home that meets MassSave's ENERGY STAR NextGen tier. The 2026 program terms require all-electric space conditioning, water heating, cooking and clothes drying; a HERS Index of 45 or lower, or at least 30 percent savings over the Massachusetts User Defined Reference Home; air leakage of 1.5 ACH50 or lower, tested by an approved HERS rating company; balanced ventilation through an ERV or HRV; an EV-ready parking space built to 225 CMR 22 section R404.4; and certification by a program-approved HERS rating company to ENERGY STAR Single-Family New Homes v3.2 (or Multifamily New Construction v1.2) and to ENERGY STAR NextGen. Testing and certification typically happen at the end of construction, around when the certificate of occupancy is received. This rebate comes in the form of a check within 4 months of the certification paperwork being provided to MassSave.
  • Induction Cooktop Adder ($20,750) : A MassSave market transformation adder of $250 per unit for installing an induction cooktop in each dwelling unit. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete.

HERS40-GAS: $0

  • No MassSave Incentive On The Mixed-Fuel Path ($0) (Program Breakdown): MassSave runs new construction buildings of four units or fewer through its single-family and townhome track, and that track is all-electric only. A home that heats with gas, or that makes its hot water with gas, earns nothing here no matter how far the envelope beats code. The gas boiler and the hot water it feeds are what close the door, so the money turns on the mechanical package rather than on the score. Every incentive dollar in this study comes from the all-electric designs.
    • IMPORTANT: The rule reads on the whole home, not on one appliance, and there is no partial credit. Putting a gas boiler or gas water heating back into an otherwise all-electric design removes the full per-home rebate for that building.
    • IMPORTANT: The four-unit line is drawn per building, not per project. A site of duplexes stays on the single-family and townhome track and its all-electric rule however many buildings are built, which is why a gas mechanical package costs the same rebate on every one of them.

Path Comparison - Net Cost Summary

Path

Total Cost $/sf

Total Incentives $/sf

Net $/sf

OpEx Factor

NEXTGEN

$42.02

$7.00

$35.39

1.01

HERS40-ELECTRIC

$46.19

$7.12

$39.54

1.01

HERS40-GAS

$48.47

$0.00

$48.84

1.01

Path Comparison - Envelope

Item

Path

Detailed Specifications

Cost $/sf

Incentive $/sf

Net $/sf

OpEx

Exterior Walls

HERS40-ELECTRIC

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-10 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

$7.72

$0.00

$7.72

0.95

HERS40-GAS

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-10 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

$7.72

$0.00

$7.72

0.95

NEXTGEN

≥ R-21 cavity insulation (2x6 @ 16" o.c.) with ≥ R-9 continuous exterior insulation. Walls to the unconditioned garage: ≥ R-21 cavity insulation (2x6 @ 16" o.c.).

$7.61

$0.00

$7.61

0.95

Below Grade Walls

HERS40-ELECTRIC

N/A

$0.00

$0.00

$0.00

1.00

HERS40-GAS

N/A

$0.00

$0.00

$0.00

1.00

NEXTGEN

N/A

$0.00

$0.00

$0.00

1.00

Corridor Walls

HERS40-ELECTRIC

N/A

$0.00

$0.00

$0.00

1.00

HERS40-GAS

N/A

$0.00

$0.00

$0.00

1.00

NEXTGEN

N/A

$0.00

$0.00

$0.00

1.00

Slab

HERS40-ELECTRIC

≥ R-20 perimeter insulation, 2 ft deep, at the interior face of the slab edge, plus ≥ R-20 under-slab insulation, 2 ft wide; provides a full thermal break.

$0.86

$0.00

$0.86

0.90

HERS40-GAS

≥ R-20 perimeter insulation, 2 ft deep, at the interior face of the slab edge, plus ≥ R-20 under-slab insulation, 2 ft wide; provides a full thermal break.

$0.86

$0.00

$0.86

0.90

NEXTGEN

≥ R-20 perimeter insulation, 2 ft deep, at the interior face of the slab edge, plus ≥ R-20 under-slab insulation, 2 ft wide; provides a full thermal break.

$0.86

$0.00

$0.86

0.90

Floor Over Unconditioned Space

HERS40-ELECTRIC

N/A

$0.00

$0.00

$0.00

1.00

HERS40-GAS

N/A

$0.00

$0.00

$0.00

1.00

NEXTGEN

N/A

$0.00

$0.00

$0.00

1.00

Floor Over Garage

HERS40-ELECTRIC

≥ R-30 cavity insulation.

$0.04

$0.00

$0.04

0.90

HERS40-GAS

≥ R-30 cavity insulation.

$0.04

$0.00

$0.04

0.90

NEXTGEN

≥ R-30 cavity insulation.

$0.04

$0.00

$0.04

0.90

Floor Over Podium

HERS40-ELECTRIC

N/A

$0.00

$0.00

$0.00

1.00

HERS40-GAS

N/A

$0.00

$0.00

$0.00

1.00

NEXTGEN

N/A

$0.00

$0.00

$0.00

1.00

Rim Joists

HERS40-ELECTRIC

≥ R-21 rim/band insulation at floor transitions.

$0.20

$0.00

$0.20

0.95

HERS40-GAS

≥ R-21 rim/band insulation at floor transitions.

$0.20

$0.00

$0.20

0.95

NEXTGEN

≥ R-21 rim/band insulation at floor transitions.

$0.20

$0.00

$0.20

0.95

Roof

HERS40-ELECTRIC

Vented attic: ≥ R-60 insulation.

$1.20

$0.00

$1.20

1.00

HERS40-GAS

Vented attic: ≥ R-60 insulation.

$1.20

$0.00

$1.20

1.00

NEXTGEN

Vented attic: ≥ R-49 insulation.

$1.07

$0.00

$1.07

1.00

Windows & Glass Doors

HERS40-ELECTRIC

High performance, U ≤ 0.18 / SHGC ≤ 0.18.

$13.88

$0.00

$13.88

1.00

HERS40-GAS

High performance, U ≤ 0.18 / SHGC ≤ 0.18.

$13.88

$0.00

$13.88

1.00

NEXTGEN

High performance, U ≤ 0.25 / SHGC ≤ 0.25.

$10.43

$0.00

$10.43

1.00

Doors

HERS40-ELECTRIC

Opaque door, U ≤ 0.20 (R-5.0).

$0.35

$0.00

$0.35

0.95

HERS40-GAS

Opaque door, U ≤ 0.20 (R-5.0).

$0.35

$0.00

$0.35

0.95

NEXTGEN

Opaque door, U ≤ 0.20 (R-5.0).

$0.35

$0.00

$0.35

0.95

Air Sealing

HERS40-ELECTRIC

≤ 1.5 ACH50; tested.

$2.10

$0.00

$2.10

0.95

HERS40-GAS

≤ 1.5 ACH50; tested.

$2.10

$0.00

$2.10

0.95

NEXTGEN

≤ 1.5 ACH50; tested.

$2.10

$0.00

$2.10

0.95

Path Comparison - Mechanical

Item

Path

Detailed Specifications

Cost $/sf

Incentive $/sf

Net $/sf

OpEx

HVAC

HERS40-ELECTRIC

Ducted air-source heat pump (as modeled); SEER2 ≥ 17.5; HSPF2 ≥ 10.5. See HVAC Design Loads.

$6.34

$0.00

$6.34

1.15

HERS40-GAS

Natural gas boiler (as modeled); AFUE ≥ 96; cooling by a separate system, cooling only; SEER2 ≥ 15.2. See HVAC Design Loads.

$8.63

$0.00

$8.63

1.10

NEXTGEN

Ducted air-source heat pump (as modeled); SEER2 ≥ 17.5; HSPF2 ≥ 10.5; 5 kW electric heat kit on every four-bedroom unit. See HVAC Design Loads.

$6.38

$0.00

$6.38

1.15

Ductwork

HERS40-ELECTRIC

Supply and return ducts in attic under insulation poorly vented insulated to code minimum; ducts in conditioned space insulated to code minimum.

$2.08

$0.00

$2.08

1.00

HERS40-GAS

Supply and return ducts in attic under insulation poorly vented insulated to code minimum; ducts in conditioned space insulated to code minimum.

$2.08

$0.00

$2.08

1.00

NEXTGEN

Supply and return ducts in attic under insulation poorly vented insulated to code minimum; ducts in conditioned space insulated to code minimum.

$2.08

$0.00

$2.08

1.00

Duct Sealing

HERS40-ELECTRIC

≤ greater of 40 CFM25 or 4 CFM25 per 100 sqft of conditioned floor area; tested at rough-in, after the HVAC is installed.

$0.43

$0.00

$0.43

1.00

HERS40-GAS

≤ greater of 40 CFM25 or 4 CFM25 per 100 sqft of conditioned floor area; tested at rough-in, after the HVAC is installed.

$0.43

$0.00

$0.43

1.00

NEXTGEN

≤ greater of 40 CFM25 or 4 CFM25 per 100 sqft of conditioned floor area; tested at rough-in, after the HVAC is installed.

$0.43

$0.00

$0.43

1.00

HVAC Grading

HERS40-ELECTRIC

Fan Flow Test: Grade I
Watt Draw Test: Grade I
Refrigerant Charge: Grade I
HVAC installer must provide photo of the digital refrigerant scale showing the amount charged, with the tank on the scale and hoses connected to the outdoor unit, along with a photo of the outdoor unit's data plate.

$0.00

$0.00

$0.00

1.00

HERS40-GAS

Fan Flow Test: Grade I
Watt Draw Test: Grade I
Refrigerant Charge: Grade I
HVAC installer must provide photo of the digital refrigerant scale showing the amount charged, with the tank on the scale and hoses connected to the outdoor unit, along with a photo of the outdoor unit's data plate.

$0.00

$0.00

$0.00

1.00

NEXTGEN

Fan Flow Test: Grade I
Watt Draw Test: Grade I
Refrigerant Charge: Grade I
HVAC installer must provide photo of the digital refrigerant scale showing the amount charged, with the tank on the scale and hoses connected to the outdoor unit, along with a photo of the outdoor unit's data plate.

$0.00

$0.00

$0.00

1.00

Mechanical Ventilation

HERS40-ELECTRIC

In-unit ERV
3-bedroom: 110 CFM, ≥ 81% ASRE
4-bedroom: 130 CFM, ≥ 79% ASRE

$1.05

$0.00

$1.05

1.20

HERS40-GAS

In-unit ERV
3-bedroom: 110 CFM, ≥ 81% ASRE
4-bedroom: 130 CFM, ≥ 79% ASRE

$1.05

$0.00

$1.05

1.20

NEXTGEN

In-unit ERV
3-bedroom: 110 CFM, ≥ 81% ASRE
4-bedroom: 130 CFM, ≥ 79% ASRE

$1.05

$0.00

$1.05

1.20

Local Mechanical Exhaust

HERS40-ELECTRIC

Bathroom(s): at least 50 CFM intermittent and up to 3.0 sones, or at least 20 CFM continuous and up to 2.0 sones.
Kitchen(s): at least 100 CFM intermittent and up to 3.0 sones, or continuous at 5 ACH.
Both: exhaust directly outdoors with ENERGY STAR certified fans. A balanced ERV or HRV serving the space may satisfy this requirement.

$0.50

$0.00

$0.50

1.05

HERS40-GAS

Bathroom(s): at least 50 CFM intermittent and up to 3.0 sones, or at least 20 CFM continuous and up to 2.0 sones.
Kitchen(s): at least 100 CFM intermittent and up to 3.0 sones, or continuous at 5 ACH.
Both: exhaust directly outdoors with ENERGY STAR certified fans. A balanced ERV or HRV serving the space may satisfy this requirement.

$0.50

$0.00

$0.50

1.05

NEXTGEN

Bathroom(s): at least 50 CFM intermittent and up to 3.0 sones, or at least 20 CFM continuous and up to 2.0 sones.
Kitchen(s): at least 100 CFM intermittent and up to 3.0 sones, or continuous at 5 ACH.
Both: exhaust directly outdoors with ENERGY STAR certified fans. A balanced ERV or HRV serving the space may satisfy this requirement.

$0.50

$0.00

$0.50

1.05

Thermostats

HERS40-ELECTRIC

Programmable thermostat (as modeled).

$0.04

$0.00

$0.04

1.05

HERS40-GAS

Programmable thermostat (as modeled).

$0.04

$0.00

$0.04

1.05

NEXTGEN

Programmable thermostat (as modeled).

$0.04

$0.00

$0.04

1.05

Path Comparison - Plumbing & Appliances

Item

Path

Detailed Specifications

Cost $/sf

Incentive $/sf

Net $/sf

OpEx

DHW

HERS40-ELECTRIC

3-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 4; 65 gal
4-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 4; 80 gal

$1.53

$0.00

$1.53

1.20

HERS40-GAS

Gas tankless water heater (as modeled); UEF ≥ 0.96.

$1.95

$0.00

$1.95

1.15

NEXTGEN

3-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 3.5; 65 gal
4-Bedroom: Heat pump water heater (HPWH) (as modeled); UEF ≥ 3.5; 80 gal

$1.42

$0.00

$1.42

1.20

DHW Piping

HERS40-ELECTRIC

Supply piping insulated to ≥ R-3.

$0.36

$0.00

$0.36

0.95

HERS40-GAS

Supply piping insulated to ≥ R-3.

$0.36

$0.00

$0.36

0.95

NEXTGEN

Supply piping insulated to ≥ R-3.

$0.36

$0.00

$0.36

0.95

Water Fixtures

HERS40-ELECTRIC

WaterSense certified (Lavatory ≤ 1.2 GPM; Shower ≤ 2.0 GPM; Kitchen ≤ 2.2 GPM).

$0.89

$0.00

$0.89

1.00

HERS40-GAS

WaterSense certified (Lavatory ≤ 1.2 GPM; Shower ≤ 2.0 GPM; Kitchen ≤ 2.2 GPM).

$0.89

$0.00

$0.89

1.00

NEXTGEN

WaterSense certified (Lavatory ≤ 1.2 GPM; Shower ≤ 2.0 GPM; Kitchen ≤ 2.2 GPM).

$0.89

$0.00

$0.89

1.00

Refrigerator

HERS40-ELECTRIC

≤ 600 kWh/yr; electric.

$0.38

$0.00

$0.38

1.10

HERS40-GAS

≤ 600 kWh/yr; electric.

$0.38

$0.00

$0.38

1.10

NEXTGEN

≤ 600 kWh/yr; electric.

$0.38

$0.00

$0.38

1.10

Dishwasher

HERS40-ELECTRIC

≤ 240 kWh/yr; electric.

$0.21

$0.00

$0.21

1.10

HERS40-GAS

≤ 240 kWh/yr; electric.

$0.21

$0.00

$0.21

1.10

NEXTGEN

≤ 240 kWh/yr; electric.

$0.21

$0.00

$0.21

1.10

Clothes Washer

HERS40-ELECTRIC

IMEF ≥ 2.06; IWF ≤ 4.2; ≤ 152 kWh/yr; electric.

$0.25

$0.00

$0.25

1.10

HERS40-GAS

IMEF ≥ 2.06; IWF ≤ 4.2; ≤ 152 kWh/yr; electric.

$0.25

$0.00

$0.25

1.10

NEXTGEN

IMEF ≥ 2.06; IWF ≤ 4.2; ≤ 152 kWh/yr; electric.

$0.25

$0.00

$0.25

1.10

Clothes Dryer

HERS40-ELECTRIC

Heat pump dryer; ventless; CEF ≥ 8.5.

$0.57

$0.00

$0.57

1.00

HERS40-GAS

Standard electric dryer; vented; CEF ≥ 3.93.

$0.27

$0.00

$0.27

1.00

NEXTGEN

Standard electric dryer; vented; CEF ≥ 3.93.

$0.27

$0.00

$0.27

1.00

Stove / Oven

HERS40-ELECTRIC

Electric induction cooktop; convection oven.

$0.39

$0.12

$0.27

1.05

HERS40-GAS

Electric range.

$0.28

$0.00

$0.28

1.00

NEXTGEN

Electric range.

$0.28

$0.00

$0.28

1.00

Path Comparison - Electrical

Item

Path

Detailed Specifications

Cost $/sf

Incentive $/sf

Net $/sf

OpEx

Lighting

HERS40-ELECTRIC

≥ 100% high-efficacy (LED).

$4.00

$0.00

$4.00

0.85

HERS40-GAS

≥ 100% high-efficacy (LED).

$4.00

$0.00

$4.00

0.85

NEXTGEN

≥ 100% high-efficacy (LED).

$4.00

$0.00

$4.00

0.85

Solar Ready

HERS40-ELECTRIC

Reserve an unobstructed rooftop solar-ready zone (at least 300 sq ft; 150 sq ft for small townhouses) with structural capacity, a conduit pathway, and reserved electrical-panel space. Waived if solar is already installed or the roof is heavily shaded.

$0.30

$0.00

$0.30

1.00

HERS40-GAS

Reserve an unobstructed rooftop solar-ready zone (at least 300 sq ft; 150 sq ft for small townhouses) with structural capacity, a conduit pathway, and reserved electrical-panel space. Waived if solar is already installed or the roof is heavily shaded.

$0.30

$0.00

$0.30

1.00

NEXTGEN

Reserve an unobstructed rooftop solar-ready zone (at least 300 sq ft; 150 sq ft for small townhouses) with structural capacity, a conduit pathway, and reserved electrical-panel space. Waived if solar is already installed or the roof is heavily shaded.

$0.30

$0.00

$0.30

1.00

EV Ready

HERS40-ELECTRIC

One 50-amp Level II EV-ready circuit per dwelling unit.

$0.33

$0.00

$0.33

1.00

HERS40-GAS

One 50-amp Level II EV-ready circuit per dwelling unit.

$0.33

$0.00

$0.33

1.00

NEXTGEN

One 50-amp Level II EV-ready circuit per dwelling unit.

$0.33

$0.00

$0.33

1.00

HPWH Ready

HERS40-ELECTRIC

N/A

$0.00

$0.00

$0.00

1.00

HERS40-GAS

N/A

$0.00

$0.00

$0.00

1.00

NEXTGEN

N/A

$0.00

$0.00

$0.00

1.00

Path Comparison - Soft Costs & Whole-Building Incentives

Item

Path

Detailed Specifications

Cost $/sf

Incentive $/sf

Net $/sf

OpEx

Paperwork & Modeling

HERS40-ELECTRIC

ENERGY STAR energy model to the ERI target, the ENERGY STAR design-review checklist, and an HVAC design report. Plus ENERGY STAR NextGen documentation: all-electric equipment and EV-charging provisions.

$0.06

$7.00

-$6.94

1.00

HERS40-GAS

ENERGY STAR energy model to the ERI target, the ENERGY STAR design-review checklist, and an HVAC design report.

$0.05

$0.00

$0.05

1.00

NEXTGEN

ENERGY STAR energy model to the ERI target, the ENERGY STAR design-review checklist, and an HVAC design report. Plus ENERGY STAR NextGen documentation: all-electric equipment and EV-charging provisions.

$0.06

$7.00

-$6.94

1.00

Testing & Verification

HERS40-ELECTRIC

ENERGY STAR field verification: pre-drywall and final inspections, blower-door and duct-leakage tests, ventilation airflow, and HVAC installation grading. Plus ENERGY STAR NextGen verification: all-electric equipment and EV-charging infrastructure.

$0.13

$0.00

$0.13

1.00

HERS40-GAS

ENERGY STAR field verification: pre-drywall and final inspections, blower-door and duct-leakage tests, ventilation airflow, and HVAC installation grading.

$0.12

$0.00

$0.12

1.00

NEXTGEN

ENERGY STAR field verification: pre-drywall and final inspections, blower-door and duct-leakage tests, ventilation airflow, and HVAC installation grading. Plus ENERGY STAR NextGen verification: all-electric equipment and EV-charging infrastructure.

$0.13

$0.00

$0.13

1.00

Additional Design Considerations Not Represented In This Study

  • N/A