CS50 Energy Code Feasibility Study in Shrewsbury, Massachusetts

Energy code feasibility study for a 36-unit 3 Story Multifamily Building in Massachusetts. Compares multiple design paths. Recommended: Path 3 - HPWH-in-Corridor. View full study.

Study Type
Energy Code Feasibility Study
State
Massachusetts
Units
36
Building Type
3 Story Multifamily Building
Fuel Type
All-Electric OR Mixed
Recommended Path
Path 3 - HPWH-in-Corridor

Goal

To find the most cost-effective compliance path, this report isolates energy code related costs from total construction. We use real bid data from vendors & clients to create a reliable framework for aligning incentives and design, with all recommendations confirmed by detailed energy modeling.

Project

  • Shrewsbury, MA 01545
  • 36 Units | 53,280 sqft
  • New Construction | 3 Story Multifamily Building
  • All-Electric | Stretch Code | All-Electric HERS ≤ 45 or Mixed-Fuel HERS ≤ 45 | ESTAR MFNC v1.2 (Optional)

Overview

Read This: This report compares different ways you can build the project and meet energy code, looking at both cost and incentives, with the ultimate goal as finding the most affordable path.

  • The overview outlines the key differences between each of the paths we show in this report and why we recommend the one we picked over the others.
  • The recommended design section is where we share the requirements and incentives for the path we think is best based on affordability.
  • The path comparison section shows the detailed requirements and incentives for each path we compared, basically showing our work if you want to dig in.

Path Summaries

Path 1: Envelope-Heavy (All-Electric, no HPWH) (Great Alternative): All-Electric HERS / ERI path with ENERGY STAR MFNC v1.2 certification. Multi-zone ductless cold-climate heat pump at HSPF2 10.0 to 10.7 / SEER2 24 to 25 (R-454B refrigerant) heats and cools every unit. Domestic hot water comes from an in-unit electric resistance storage tank at UEF 0.93, which keeps the DHW system simple at the cost of an aggressive envelope. Walls are 2x6 cavity ccSPF at R-38 (no continuous insulation), windows are triple pane low-E argon at U-0.15 / SHGC 0.20, and the unvented flat roof runs R-60 ccSPF + ocSPF. The higher-efficiency CCHP units (Carrier 37M Series, HSPF2 10.0-10.7) are the key that makes this all-electric path work without HPWH. Net cost: $29.82/sf with $102,600-$156,600 in incentives.

Path 2: All-Gas Combi (Mixed-Fuel): Mixed-Fuel HERS / ERI path under the stricter mixed-fuel HERS 42 ceiling. Heating comes from a Navien-class gas combi boiler at AFUE 0.95 feeding a hydronic coil in a ducted air handler; cooling comes from a rooftop DX condenser at SEER2 16. The same combi serves DHW at UEF 0.96, eliminating the need for a separate water heater. Walls are 2x6 cavity ccSPF at R-38, windows are vinyl double-pane at U-0.27 / SHGC 0.30, and the roof runs R-60 ccSPF + ocSPF. Gas heating disqualifies the project from MassSave incentives. Net cost: $31.21/sf with minimal incentives.

Path 3: HPWH-in-Corridor (Recommended): All-Electric HERS / ERI path with ENERGY STAR MFNC v1.2 certification. Multi-zone ductless cold-climate heat pump at HSPF2 9.0 to 9.5 / SEER2 18.5 to 19.5 heats and cools every unit. The heat pump water heater (UEF 3.5, 50 gal for 1BR units and 65 gal for 2BR units) is placed in the conditioned corridor rather than inside each dwelling, removing it from the resident's daily experience while keeping the unit HERS load benefit. The corridor placement is worth approximately 1 to 2 HERS points relative to in-unit HPWH because the unit avoids the dehumidification cooling penalty in summer and the heating trade-off in winter. Walls are a lighter R-30 ccSPF in 2x6 cavity, windows are vinyl double-pane at U-0.30 / SHGC 0.30, and the roof runs R-49 ccSPF + ocSPF. Recommended as the lowest net cost path at $24.52/sf with $93,600-$104,400 in incentives.

Code Path Description

All three paths are evaluated against 225 CMR 22 (Massachusetts Stretch Energy Code, 2025 edition), the residential energy code applicable to multifamily buildings of three stories or fewer in Shrewsbury, MA (Stretch Code adopted 1/1/2017). Compliance is via the Energy Rating Index path (R406) using ANSI / RESNET / ICC 301 modeling per IECC 2021 as amended by 225 CMR 22. Climate Zone 5A applies.

Path 1 and Path 3 follow RC103.2 (All-Electric Pathway). The maximum HERS Index is 45. Solar-ready and EV-ready provisions per Appendix RB and R404.4 apply; no on-site renewable energy installation is required for the All-Electric path.

Path 2 follows RC104.2 (Mixed-Fuel Pathway). The maximum HERS Index is 42. Per RC104.3, electric-readiness must be provided for any installed gas appliances (space heat, water heat, range, dryer): dedicated branch circuits and condensate provisions are required even though the equipment will be installed gas in this path.

ENERGY STAR Multifamily New Construction v1.2 is pursued on all three paths as a voluntary certification for incentive purposes. The ENERGY STAR ERI Target is computed against the Multifamily Reference Design at modeling time and varies by unit type; ECC default placeholder is HERS 45 for the All-Electric paths; final target reads from Ekotrope at the per-unit level during Phase 3.

Municipality Requirements

Code Path Table

Code Path

Code Path Code Path Detail

Recommended Design - Incentives

Incentives Available: $102,600 - $156,600

  • MassSave Multifamily Low Rise Program Energy Star Tier ($90,000): You get this rebate for having your building(s) certified for the Energy Star MFNC v1.2 program. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • MassSave Multifamily Heat Pump Water Heater Adder ($9,000): You get this rebate for installing heat pump water heaters in your units. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • MassSave Multifamily Wifi Enabled Thermostat Adder ($3,600): You get this rebate for installing wifi enabled thermostats in your units. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • DOER Alternative Energy Credits ($0 - $51,000): This rebate is received for installing APS eligible air source heat pumps (click here for the list). There is an extensive process to get this incentive. It comes in the form of a check approximately 6-12 months after the heat pumps are installed and fully operational. IMPORTANT: Although an estimate is provided, this incentive can vary widely typically between $300-1,500 per heat pump. It's based on expected kWh usage of the system as well as the market value of the alternative energy credits when sold. (Program Breakdown)

Recommended Design - Units

ItemDetailed Specifications
Exterior WallsR-30 ccSPF in 2x6 cavity @ 16 oc; ZIP sheathing
SlabR-10 XPS perimeter 4 ft
Rim Joists3" ccSPF (R-21)
RoofSealed (unvented) flat roof; R-49 ccSPF + ocSPF assembly
Windows & Glass DoorsVinyl double-pane low-E argon; U-0.30; SHGC 0.30
DoorsInsulated opaque entry; R-4.75
Air SealingTested 0.30 CFM50/sf shell
HVACMulti-zone ductless cold-climate heat pump; HSPF2 9.0 to 9.5; SEER2 18.5 to 19.5; ENERGY STAR Cold Climate. A units: 2-zone outdoor + 2 indoor heads, 1.5T (1BR Product Rec). B/C/D units: 3-zone outdoor + 3 indoor heads, 2T (2BR Product Rec). E units: 3-zone outdoor + 3 indoor heads, 2.5T (2BR+ Product Rec). Indoor heads: wall-mount ductless (Indoor head Product Rec).
DuctworkN/A
Duct Sealing & TestN/A
HVAC GradingN/A
Mechanical VentilationERV; sized per ASHRAE 62.2 (50 CFM 1BR / 65 CFM 2BR); 87/84% SRE at design CFM (Product Rec).
Local Mechanical ExhaustBathroom(s): ≥50 CFM intermittent & ≤3.0 sones OR ≥20 CFM continuous & ≤2.0 sones. Kitchen(s): ≥100 CFM intermittent & ≤3.0 sones OR continuous, ≥5 ACH. Both: Exhaust directly outdoors, ENERGY STAR certified, utilize ERV.
ThermostatsProgrammable smart thermostat per zone (Product Rec).
DHWHPWH; 50 gal (1BR) (1BR) / 65 gal (2BR) (2BR), UEF 3.5; located in conditioned corridor
DHW PipingR-3 pipe insulation on all hot water lines. Maximum trunk-to-fixture pipe length: 1BR ≤42 ft, 2BR ≤48 ft. No recirculation.
Water FixturesLow-flow WaterSense certified ≤1.8 GPM showerhead, ≤1.5 GPM lavatory faucet, ≤1.8 GPM kitchen faucet
RefrigeratorENERGY STAR; 450 kWh/yr (1BR), 550 kWh/yr (2BR) (Product Rec).
Dishwasher240 kWh/yr; standard efficiency; ENERGY STAR (Product Rec).
Clothes WasherFront-load IMEF 2.92; IWF 2.9; 99 kWh/yr; 5.0 cu ft; ENERGY STAR Most Efficient (Product Rec).
Clothes DryerHeat-pump ventless; CEF 9.0; 266 kWh/yr; 7.8 cu ft; ENERGY STAR Most Efficient
Stove / OvenStandard electric oven/stove
Lighting100% LED
Solar ReadyDesignated Solar Zone: Reserve a contiguous area equal to at least 40% of the total horizontal roof area; free of obstructions, minimum 5 ft wide; 5 PSF collateral dead load; conduit pathways and reserved breaker space.
EV ReadyEV Ready infrastructure for at least 20% of total parking. Branch circuit and termination for required spaces, rated for at least 6.2 kVA per space.
Paperwork & ModelingHERS/ERI energy model, 2021 IECC checklists, ENERGY STAR checklists, incentive documentation.
Testing & VerificationUnit Blower Door Test, Mechanical Ventilation Testing, Room Balancing, Predrywall & Final Inspection.

Recommended Design - Common Space

ItemDetailed Specifications
Exterior WallsR-30 ccSPF in 2x6 cavity @ 16 oc; ZIP sheathing
Below-Grade WallsR-7.5 CI
SlabR-10 XPS perimeter 4 ft
Rim JoistsSeal interior rim cavity with minimum 3" closed-cell spray foam
RoofSealed (unvented) flat roof; R-49 ccSPF + ocSPF assembly
WindowsFixed: U-0.36 / SHGC 0.40; Operable: U-0.43 / SHGC 0.40
DoorsEntrance: U-0.77 / SHGC 0.40; Opaque: U-0.61
Air SealingWhole-building air barrier per 2024 IECC C402.5. Materials-based compliance (assemblies ≤0.04 cfm/ft² per ASTM E2357) or whole-building pressurization testing (≤0.27 CFM50/ft² at 50 Pa).
HVACDucted split heat pump; SEER2 ≥15.2 / HSPF2 ≥7.8 / EER2 ≥11.7; ENERGY STAR certified; sized per Manual J/S, ≤15% above calculated cooling load.
Duct Sealing≤8 CFM25 per 100 ft² CFA or 80 CFM, whichever is greater.
Mechanical VentilationPer ASHRAE 62.1: Lobby/Office 5 cfm/person + 0.06 cfm/ft²; Fitness 20 cfm/person + 0.18 cfm/ft²; Corridor 0.06 cfm/ft²; Laundry 5 cfm/person + 0.12 cfm/ft². ERV required if total OA intake ≥1,000 cfm. Demand controlled ventilation required for spaces >500 ft² with occupancy >25 people per 1,000 ft².
Local Mechanical ExhaustPer ASHRAE 62.1 exhaust rates. Common restrooms, laundry, mechanical rooms as applicable.
ThermostatsProgrammable with 5°F setback capability during unoccupied periods.
DHWPoint-of-use electric water heater for common restroom sinks (if applicable).
DHW PipingPiping insulated to R-3 (≤1.5" pipe) / R-4 (>1.5" pipe).
Water FixturesWaterSense certified: Lavatory ≤1.5 GPM; Toilet ≤1.28 GPF; Urinal (if installed) ≤0.5 GPF.
Lighting100% LED. LPD limits by space: Corridor 0.41 W/ft²; Lobby 0.84; Office 0.74; Fitness 0.63; Community Room 0.59; Laundry 0.53; Stairway 0.49; Mechanical/Electrical 0.43; Storage 0.38.
Lighting ControlsOccupancy/vacancy sensors in all common spaces (corridors/stairs may dim to 50% instead of off). Daylight responsive controls where daylighted area >150 ft². Automatic time switches on all common area lighting.
Solar ReadyPer dwelling unit table (building-wide requirement).
EV ReadyPer dwelling unit table (building-wide requirement).
Paperwork & ModelingCOMcheck report for common areas, ASHRAE 62.1 ventilation calcs, lighting power density calcs.
Testing & VerificationMechanical ventilation balancing, lighting controls commissioning, rough-in and final inspection.

Exterior Wall Assembly (Recommended Path)

Exterior Wall Assembly

Rim Joist (Recommended Path)

Rim Joist Assembly

Roof (Recommended Path)

Roof Assembly

Slab Edge (Recommended Path)

Slab Edge Assembly

Path Comparison - Incentives

Path 1: $102,600 - $156,600

  • MassSave Multifamily Low Rise Program Energy Star Tier ($90,000): You get this rebate for having your building(s) certified for the Energy Star MFNC v1.2 program. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • MassSave Multifamily Heat Pump Water Heater Adder ($9,000): You get this rebate for installing heat pump water heaters in your units. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • MassSave Multifamily Wifi Enabled Thermostat Adder ($3,600): You get this rebate for installing wifi enabled thermostats in your units. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • DOER Alternative Energy Credits ($0 - $51,000): This rebate is received for installing APS eligible air source heat pumps (click here for the list). There is an extensive process to get this incentive. It comes in the form of a check approximately 6-12 months after the heat pumps are installed and fully operational. IMPORTANT: Although an estimate is provided, this incentive can vary widely typically between $300-1,500 per heat pump. It's based on expected kWh usage of the system as well as the market value of the alternative energy credits when sold. (Program Breakdown)

Path 2: N/A - Gas Heating Disqualifies You From MassSave

Path 3: $93,600 - $104,400

  • MassSave Multifamily Low Rise Program Energy Star Tier ($90,000): You get this rebate for having your building(s) certified for the Energy Star MFNC v1.2 program. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • MassSave Multifamily Wifi Enabled Thermostat Adder ($3,600): You get this rebate for installing wifi enabled thermostats in your units. This requires pre-approval via an application to be submitted before construction starts. This rebate comes in the form of a check within 4 months of certification documentation being provided to MassSave, typically this is 4 months after construction is complete. (Program Breakdown)
  • DOER Alternative Energy Credits ($0 - $51,000): This rebate is received for installing APS eligible air source heat pumps (click here for the list). There is an extensive process to get this incentive. It comes in the form of a check approximately 6-12 months after the heat pumps are installed and fully operational. IMPORTANT: Although an estimate is provided, this incentive can vary widely typically between $300-1,500 per heat pump. It's based on expected kWh usage of the system as well as the market value of the alternative energy credits when sold. (Program Breakdown)

Path Comparison - Net Cost Summary

PathTotal Cost $/sfTotal Incentives $/sfNet $/sfOpEx FactorWorst HERS$/HERS Point
Path 1$34.20$3.46$29.820.9744.67$0.67
Path 2$32.30$0.77$31.210.9941.50$0.75
Path 3 (Recommended)$27.40$2.63$24.520.9938.79$0.63

Path Comparison - Envelope

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
Exterior WallsPath 1R-38 ccSPF in 2x6 cavity @ 16 oc; ZIP sheathing$4.50$0.00$4.500.85
Exterior WallsPath 2R-38 ccSPF in 2x6 cavity @ 16 oc; ZIP sheathing$4.50$0.00$4.500.85
Exterior WallsPath 3R-30 ccSPF in 2x6 cavity @ 16 oc; ZIP sheathing$3.80$0.00$3.800.85
SlabPath 1R-10 XPS perimeter 4 ft + R-10 underslab$1.80$0.00$1.800.90
SlabPath 2R-10 XPS perimeter 4 ft + R-10 underslab$1.80$0.00$1.800.90
SlabPath 3R-10 XPS perimeter 4 ft$1.20$0.00$1.200.90
Rim JoistsPath 13" ccSPF (R-21)$0.20$0.00$0.200.85
Rim JoistsPath 23" ccSPF (R-21)$0.20$0.00$0.200.85
Rim JoistsPath 33" ccSPF (R-21)$0.20$0.00$0.200.85
RoofPath 1Sealed (unvented) flat roof; R-60 ccSPF + ocSPF assembly$3.50$0.00$3.500.95
RoofPath 2Sealed (unvented) flat roof; R-60 ccSPF + ocSPF assembly$3.50$0.00$3.500.95
RoofPath 3Sealed (unvented) flat roof; R-49 ccSPF + ocSPF assembly$3.50$0.00$3.500.95
Windows & Glass DoorsPath 1Triple pane low-E argon; U-0.15; SHGC 0.20$8.20$0.00$8.201.00
Windows & Glass DoorsPath 2Vinyl double-pane low-E argon; U-0.27; SHGC 0.30$4.20$0.00$4.201.00
Windows & Glass DoorsPath 3Vinyl double-pane low-E argon; U-0.30; SHGC 0.30$3.80$0.00$3.801.00
DoorsPath 1Insulated opaque entry; R-4.75$0.20$0.00$0.201.00
DoorsPath 2Insulated opaque entry; R-6$0.25$0.00$0.251.00
DoorsPath 3Insulated opaque entry; R-4.75$0.20$0.00$0.201.00
Air SealingPath 1Tested 0.27 CFM50/sf shell$0.40$0.00$0.400.85
Air SealingPath 2Tested 0.27 CFM50/sf shell$0.40$0.00$0.400.85
Air SealingPath 3Tested 0.30 CFM50/sf shell$0.30$0.00$0.300.85

Path Comparison - Mechanical

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
HVACPath 1Multi-zone ductless cold-climate heat pump; HSPF2 10.0 to 10.7; SEER2 24 to 25; ENERGY STAR Cold Climate; R-454B refrigerant. A units: 2-zone outdoor + 2 indoor heads, 1.5T (1BR Product Rec). B/C/D units: 3-zone outdoor + 3 indoor heads, 2T (2BR Product Rec). E units: 3-zone outdoor + 3 indoor heads, 2.5T (2BR+ Product Rec). Indoor heads: wall-mount ductless (Indoor head Product Rec).$8.50$0.20$8.301.10
HVACPath 2Hydronic-coil ducted air handler + rooftop DX condenser. Heating: AFUE 0.95, hot water fed by the gas combi boiler. Cooling: SEER2 16. Capacity matched per unit type. (Air Handler Product Rec) (Condenser Product Rec).$8.20$0.20$8.001.15
HVACPath 3Multi-zone ductless cold-climate heat pump; HSPF2 9.0 to 9.5; SEER2 18.5 to 19.5; ENERGY STAR Cold Climate. A units: 2-zone outdoor + 2 indoor heads, 1.5T (1BR Product Rec). B/C/D units: 3-zone outdoor + 3 indoor heads, 2T (2BR Product Rec). E units: 3-zone outdoor + 3 indoor heads, 2.5T (2BR+ Product Rec). Indoor heads: wall-mount ductless (Indoor head Product Rec).$6.50$0.20$6.301.10
DuctworkPath 1N/A$0.00$0.00$0.001.00
DuctworkPath 2Supply/return ducts in conditioned space; R-6$1.80$0.00$1.801.05
DuctworkPath 3N/A$0.00$0.00$0.001.00
Duct Sealing & TestPath 1N/A$0.00$0.00$0.001.00
Duct Sealing & TestPath 2The greater of 8 CFM25/100 ft² conditioned floor area or 80 CFM25 to outside (duct sealing protocol).$0.20$0.00$0.201.00
Duct Sealing & TestPath 3N/A$0.00$0.00$0.001.00
HVAC GradingPath 1N/A$0.30$0.20$0.101.00
HVAC GradingPath 2N/A$0.30$0.20$0.101.00
HVAC GradingPath 3N/A$0.30$0.20$0.101.00
Mechanical VentilationPath 1ERV; sized per ASHRAE 62.2 (50 CFM 1BR / 65 CFM 2BR); 87/84% SRE at design CFM (Product Rec).$1.20$0.30$0.901.05
Mechanical VentilationPath 2ERV; sized per ASHRAE 62.2 (50 CFM 1BR / 65 CFM 2BR); 87/84% SRE at design CFM (Product Rec).$1.20$0.30$0.901.05
Mechanical VentilationPath 3ERV; sized per ASHRAE 62.2 (50 CFM 1BR / 65 CFM 2BR); 87/84% SRE at design CFM (Product Rec).$1.20$0.30$0.901.05
Local Mechanical ExhaustPath 1Bathroom(s): ≥50 CFM intermittent & ≤3.0 sones OR ≥20 CFM continuous & ≤2.0 sones. Kitchen(s): ≥100 CFM intermittent & ≤3.0 sones OR continuous, ≥5 ACH. Both: Exhaust directly outdoors, ENERGY STAR certified, utilize ERV.$0.30$0.00$0.301.00
Local Mechanical ExhaustPath 2Bathroom(s): ≥50 CFM intermittent & ≤3.0 sones OR ≥20 CFM continuous & ≤2.0 sones. Kitchen(s): ≥100 CFM intermittent & ≤3.0 sones OR continuous, ≥5 ACH. Both: Exhaust directly outdoors, ENERGY STAR certified, utilize ERV.$0.30$0.00$0.301.00
Local Mechanical ExhaustPath 3Bathroom(s): ≥50 CFM intermittent & ≤3.0 sones OR ≥20 CFM continuous & ≤2.0 sones. Kitchen(s): ≥100 CFM intermittent & ≤3.0 sones OR continuous, ≥5 ACH. Both: Exhaust directly outdoors, ENERGY STAR certified, utilize ERV.$0.30$0.00$0.301.00
ThermostatsPath 1Programmable smart thermostat per zone (Product Rec).$0.20$0.07$0.151.00
ThermostatsPath 2Programmable smart thermostat (Product Rec).$0.10$0.07$0.051.00
ThermostatsPath 3Programmable smart thermostat per zone (Product Rec).$0.20$0.07$0.151.00

Path Comparison - Plumbing & Appliances

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
DHWPath 1Electric resistance storage tank; UEF 0.93; 50 gal; in-unit (Product Rec).$1.20$0.00$1.200.90
DHWPath 2Gas tankless combi (shared with hydronic heat); UEF 0.96; 199 kBTU/h (Product Rec).$1.80$0.00$1.801.10
DHWPath 3HPWH; 50 gal (1BR) (1BR) / 65 gal (2BR) (2BR), UEF 3.5; located in a conditioned corridor$2.40$0.17$2.231.20
DHW PipingPath 1R-3 pipe insulation on all hot water lines. Maximum trunk-to-fixture pipe length: 1BR ≤25 ft, 2BR ≤28 ft. No recirculation.$0.30$0.00$0.301.00
DHW PipingPath 2R-3 pipe insulation on all hot water lines. Maximum trunk-to-fixture pipe length: 1BR ≤37 ft, 2BR ≤43 ft. No recirculation.$0.30$0.00$0.301.00
DHW PipingPath 3R-3 pipe insulation on all hot water lines. Maximum trunk-to-fixture pipe length: 1BR ≤42 ft, 2BR ≤48 ft (plus 5 ft for corridor-to-unit run). No recirculation.$0.35$0.00$0.351.00
Water FixturesPath 1Low-flow WaterSense certified ≤1.8 GPM showerhead, ≤1.5 GPM lavatory faucet, ≤1.8 GPM kitchen faucet$0.10$0.00$0.100.95
Water FixturesPath 2Low-flow WaterSense certified ≤1.8 GPM showerhead, ≤1.5 GPM lavatory faucet, ≤1.8 GPM kitchen faucet$0.10$0.00$0.100.95
Water FixturesPath 3Low-flow WaterSense certified ≤1.8 GPM showerhead, ≤1.5 GPM lavatory faucet, ≤1.8 GPM kitchen faucet$0.10$0.00$0.100.95
RefrigeratorPath 1ENERGY STAR Most Efficient; 370 kWh/yr (1BR), 450 kWh/yr (2BR) (Product Rec).$0.40$0.00$0.401.00
RefrigeratorPath 2ENERGY STAR; 450 kWh/yr (1BR), 550 kWh/yr (2BR) (Product Rec).$0.35$0.00$0.351.00
RefrigeratorPath 3ENERGY STAR; 450 kWh/yr (1BR), 550 kWh/yr (2BR) (Product Rec).$0.35$0.00$0.351.00
DishwasherPath 1240 kWh/yr; standard efficiency; ENERGY STAR (Product Rec).$0.20$0.00$0.201.00
DishwasherPath 2240 kWh/yr; standard efficiency; ENERGY STAR (Product Rec).$0.20$0.00$0.201.00
DishwasherPath 3240 kWh/yr; standard efficiency; ENERGY STAR (Product Rec).$0.20$0.00$0.201.00
Clothes WasherPath 1Front-load IMEF 2.92; IWF 2.9; 99 kWh/yr; 5.0 cu ft; ENERGY STAR Most Efficient (Product Rec).$0.45$0.00$0.451.00
Clothes WasherPath 2Front-load IMEF 2.92; IWF 2.9; 99 kWh/yr; 5.0 cu ft; ENERGY STAR Most Efficient (Product Rec).$0.45$0.00$0.451.00
Clothes WasherPath 3Front-load IMEF 2.92; IWF 2.9; 99 kWh/yr; 5.0 cu ft; ENERGY STAR Most Efficient (Product Rec).$0.45$0.00$0.451.00
Clothes DryerPath 1Heat-pump ventless; CEF 9.0; 266 kWh/yr; 7.8 cu ft; ENERGY STAR Most Efficient$0.50$0.00$0.501.05
Clothes DryerPath 2Heat-pump ventless; CEF 9.0; 266 kWh/yr; 7.8 cu ft; ENERGY STAR Most Efficient$0.50$0.00$0.501.05
Clothes DryerPath 3Heat-pump ventless; CEF 9.0; 266 kWh/yr; 7.8 cu ft; ENERGY STAR Most Efficient$0.50$0.00$0.501.05
Stove / OvenPath 1Induction & convection electric oven/cooktop (Product Rec).$0.40$1.00-$0.601.00
Stove / OvenPath 2Standard electric oven/stove$0.20$0.00$0.201.00
Stove / OvenPath 3Standard electric oven/stove$0.20$0.00$0.201.00

Path Comparison - Electrical

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
LightingPath 1100% LED$0.20$0.00$0.200.85
LightingPath 2100% LED$0.20$0.00$0.200.85
LightingPath 3100% LED$0.20$0.00$0.200.85
Solar ReadyPath 1Designated Solar Zone: Reserve a contiguous area equal to at least 40% of the total horizontal roof area; free of obstructions, minimum 5 ft wide; 5 PSF collateral dead load; conduit pathways and reserved breaker space.$0.05$0.00$0.051.00
Solar ReadyPath 2Designated Solar Zone: Reserve a contiguous area equal to at least 40% of the total horizontal roof area; free of obstructions, minimum 5 ft wide; 5 PSF collateral dead load; conduit pathways and reserved breaker space.$0.05$0.00$0.051.00
Solar ReadyPath 3Designated Solar Zone: Reserve a contiguous area equal to at least 40% of the total horizontal roof area; free of obstructions, minimum 5 ft wide; 5 PSF collateral dead load; conduit pathways and reserved breaker space.$0.05$0.00$0.051.00
EV ReadyPath 1EV Ready infrastructure for at least 20% of total parking. Branch circuit and termination for required spaces, rated for at least 6.2 kVA per space.$0.40$0.00$0.401.00
EV ReadyPath 2EV Ready infrastructure for at least 20% of total parking. Branch circuit and termination for required spaces, rated for at least 6.2 kVA per space.$0.40$0.00$0.401.00
EV ReadyPath 3EV Ready infrastructure for at least 20% of total parking. Branch circuit and termination for required spaces, rated for at least 6.2 kVA per space.$0.40$0.00$0.401.00

Path Comparison - Soft Costs

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
Paperwork & ModelingPath 1HERS/ERI energy model, 2021 IECC checklists, ENERGY STAR checklists, incentive documentation.$0.40$0.00$0.401.00
Paperwork & ModelingPath 2HERS/ERI energy model, 2021 IECC checklists.$0.40$0.00$0.401.00
Paperwork & ModelingPath 3HERS/ERI energy model, 2021 IECC checklists, ENERGY STAR checklists, incentive documentation.$0.40$0.00$0.401.00
Testing & VerificationPath 1Unit Blower Door Test, Mechanical Ventilation Testing, Room Balancing, Predrywall & Final Inspection.$0.30$1.69-$1.391.00
Testing & VerificationPath 2Unit Blower Door Test, Mechanical Ventilation Testing, Predrywall & Final Inspection.$0.40$0.00$0.401.00
Testing & VerificationPath 3Unit Blower Door Test, Mechanical Ventilation Testing, Room Balancing, Predrywall & Final Inspection.$0.30$1.69-$1.391.00

Additional Design Considerations Not Represented In This Study

Slab Insulation Beyond R-10 + R-10: Tested R-15 perimeter + R-15 underslab and R-20 + R-20 extreme variants on the worst-case A-LL-I unit. Both gave less than 0.1 HERS pts of additional improvement over R-10 + R-10 (which already provides full underslab coverage). The cost premium for thicker XPS does not pencil out against the marginal HERS gain. R-10 + R-10 is the spec across all paths' LL units; R-10 perimeter only is sufficient for Path 3.

Slab Perimeter Depth 4 ft to 6 ft: Tested deepening the perimeter XPS from 4 ft to 6 ft on A-LL-I. Zero HERS impact. Frost-line coverage is not energy-relevant once the perimeter break is established at 4 ft in CZ 5A.

Rim Joist R-21 to R-30: Tested bumping rim joist ccSPF from R-21 (3 in) to R-30 (4 in). Marginal HERS impact, well under 0.05 pts. R-21 is the spec across all paths.

Hot Water Pipe Length Tightening: Standard MF default is 1/2 of the RESNET 301 formula. Tested tightening to 1/3 (the floor allowed by DEFAULTS for MF projects). Zero measurable HERS impact in this archetype's regime, where DHW load is dominated by tank standby loss rather than pipe loss. The 1/3 spec is included on Path 1 anyway since it costs nothing in installed scope, but it was not load-bearing.

Dishwasher Efficiency Upgrade: Tested swapping the 240 kWh/yr standard ENERGY STAR dishwasher for a top-tier 150 kWh/yr model. About 0.01 HERS pts of improvement; the appliance line is not a meaningful HERS lever in this build. Standard 240 kWh ENERGY STAR is retained on all paths.

Water Heater Tank Size Optimization (Path 1): Tested 30, 40, and 50 gallon variants of the electric resistance tank in Path 1. The 30 gal variant performed slightly worse (less buffer means more recovery cycling); 40 gal and 50 gal were within 0.1 HERS pts of each other. The 50 gal default tank with UEF 0.93 is the spec since it is the most common product on the shelf.

Marathon-Class Premium Tank UEF 0.95: Tested upgrading from a standard UEF 0.93 / 50 gal electric tank to a Marathon-class UEF 0.95 / 40 gal tank on Path 1. The HERS uplift was 0.5 pts; the cost premium per unit is approximately $600 plus extra installation steps. Standard UEF 0.93 / 50 gal retained because the path passes without the premium.

Mitsubishi MXZ Class HVAC (Path 1 baseline): Path 1 was originally modeled with Mitsubishi MXZ-2C / MXZ-3C class multi-zone systems at HSPF2 9.0 to 9.5. The path was blocked at HERS 47.72 even after the full envelope ladder. Switching to Carrier 37M Series multi-zone CCHP (HSPF2 10.0 to 10.7, SEER2 24 to 25, R-454B refrigerant, all ENERGY STAR Cold Climate certified) was the largest single unlock at approximately 1 HERS point of improvement.

Triple-Pane Windows on Paths 2 and 3: Triple pane at U-0.15 was tested as a last-resort knob on Path 1 and was load-bearing there (about 0.5 to 0.6 HERS pts vs U-0.27 double pane). Tested on Path 2 and Path 3, the gain was significantly smaller because those paths' DHW efficiency (gas combi or HPWH-in-corridor) already delivers the major HERS lift. Vinyl double pane at U-0.27 (Path 2) and U-0.30 (Path 3) is the spec.

Continuous Insulation (CI): All three paths route around CI by using full-cavity ccSPF (R-30 or R-38) instead. The R-value parity comes from spray foam's better effective R per inch and continuous air-barrier effect, so the model performance is comparable without the exterior detailing complexity.

HPWH In-Unit Placement: Tested HPWH placement inside the dwelling unit (the standard install) versus the conditioned corridor. The corridor placement on Path 3 is worth approximately 1 to 2 HERS pts relative to in-unit HPWH because the unit avoids the dehumidification cooling penalty in summer and the heating trade-off in winter.

Gas Range on Path 2: Tested explicitly on the Path 2 worst-case D-LL-C unit. Switching from gas to electric range yielded 1.5 HERS points of improvement. The gas range was dropped after that test; electric range is used in all three paths' final specs.