CS49 Energy Code Feasibility Study in Lexington, Massachusetts

Energy code feasibility study for a 40-unit 3 Story Multifamily Building Over Underground Podium Parking in Massachusetts. Compares multiple design paths. Recommended: ZIP System. View full study.

Study Type
Energy Code Feasibility Study
State
Massachusetts
Units
40
Building Type
3 Story Multifamily Building Over Underground Podium Parking
Fuel Type
All-Electric
Recommended Path
ZIP System

Goal

To find the most cost-effective compliance path, this report isolates energy code related costs from total construction. We use real bid data from vendors & clients to create a reliable framework for aligning incentives and design, with all recommendations confirmed by detailed energy modeling.

Project

  • Lexington, MA 02421
  • 40 Units | 64,905 sqft
  • New Construction | 3 Story Multifamily Building Over Underground Podium Parking
  • All-Electric | Specialized Opt-In | PHIUS CORE 2024 | ESTAR MFNC v1.2

Overview

Read This: This report compares different ways you can build the project and meet energy code, looking at both cost and incentives, with the ultimate goal as finding the most affordable path.

  • The overview outlines the key differences between each of the paths we show in this report and why we recommend the one we picked over the others.
  • The recommended design section is where we share the requirements and incentives for the path we think is best based on affordability.
  • The path comparison section shows the detailed requirements and incentives for each path we compared, basically showing our work if you want to dig in.

Path Summaries

Path A: Same PHIUS certification and ENERGY STAR MFNC path as Path B, with the same R-60 polyiso roof, in-unit electric tank water heaters, and ducted split heat pumps (SEER2 17-17.5 / HSPF2 9). Uses 3" ROCKWOOL Comfortboard 80 continuous insulation secured with Technoform thermal isolator clips plus R-21 batt in the cavity, and Henry Blueskin VP100 self-adhered membrane as the primary wall air barrier. This combination runs roughly $0.35/sf higher on the wall and requires the separate VP100 membrane and Technoform clip installation that Path B eliminates. Not recommended due to higher construction cost with no incentive or performance advantage over Path B. Net cost: $44.06/sf.

Path B (Recommended): PHIUS certification and ENERGY STAR MFNC path using 2.5" ZIP System R-Sheathing (R-12.6 integrated into the sheathing panel) plus R-21 batt in the cavity, R-60 polyiso roof, in-unit electric tank water heaters, and ducted split heat pumps. ZIP tape serves as the primary air barrier across the wall field, eliminating both the Technoform thermal isolator clips and the separate Henry Blueskin VP100 membrane required on Paths A and C. This reduces wall cost by roughly $0.35/sf versus Path A and simplifies the air barrier scope. All $175,000 in MassSave Passive House incentives are available. Recommended as the lowest net cost path at $42.22/sf.

Path C: Same PHIUS certification and ENERGY STAR MFNC path, with the same ROCKWOOL Comfortboard CI wall, VP100 air barrier, and ducted split heat pumps as Path A. Removes the R-21 batt from the wall cavity, swaps the R-60 roof for a thinner R-50 polyiso roof (9" instead of 11"), and replaces the in-unit electric tank water heaters with heat pump water heaters (UEF ≥3.45). The reduced envelope is offset by the higher-efficiency HPWHs, keeping the project in compliance. Not recommended because the HPWH cost premium ($3.40/sf vs. $1.15/sf) more than offsets the envelope savings, and the higher HPWH operating load adversely affects the PHIUS energy balance. Net cost: $46.17/sf.

Code Path

Code PathCode Path Detail

Recommended Design - Incentives

Available Incentives: $175,000 (All Paths)

  • MassSave Passive House Feasibility Study ($5,000): Rebate for completing a PHIUS feasibility study and a 1-hour charette with the design team and MassSave representative before construction is complete. Paid as a check within 4 months of the charette. IMPORTANT: Capped at 100% of the applicable service charge.
  • MassSave Passive House Energy Model ($20,000): Rebate for completing a PHIUS energy model and a 1-hour charette with the design team and MassSave representative before construction is complete. Paid as a check within 4 months of the meeting. IMPORTANT: Capped at 75% of the applicable service charge.
  • MassSave Passive House Pre-Certification ($30,000): Rebate for achieving PHIUS pre-certification toward the end of the pre-construction phase. Paid as a check within 4 months of pre-certification paperwork being provided to MassSave.
  • MassSave Passive House Certification ($120,000): Rebate for achieving PHIUS certification at the end of construction around certificate of occupancy. Paid as a check within 4 months of certification paperwork being provided to MassSave.
  • DOER Alternative Energy Credits (N/A - Ducted Systems Do Not Qualify): This rebate is received for installing APS eligible air source heat pumps. Ducted systems on this project do not qualify. IMPORTANT: Although an estimate is provided where applicable, this incentive can vary widely between $300-1,500 per heat pump based on expected kWh usage and market value of alternative energy credits when sold.

Recommended Design Specifications (Path B)

ItemDetailed Specifications
Exterior WallsR-12.6 - 2.5" ZIP System Insulated R-Sheathing & R-21 batt insulation in cavity
Floor Over GarageSteel Frame Slab: R-38 batt insulation resting on drop ceiling (must use thermally broken ceiling system). Post Tensioned Slab: R-30 continuous insulation on either side of the slab. Note: Either of these options work.
Rim JoistsSeal interior rim cavity with minimum 3" closed-cell spray foam for air sealing and thermal performance. Continuous Insulation shall continue over floor transitions without interruption.
Roof11" Rigid Polyiso Continuous Insulation (R-60) installed in multiple layers with staggered joints on the roof deck.
WindowsWeighted Avg: U-0.15 / SHGC 0.20
DoorsGlazed: U-0.15 / SHGC 0.20; Opaque: U-0.21 (R-4.75)
Air SealingUnits: ≤0.30 CFM50/sqft; Whole Building: ≤0.06 CFM50/sqft. ZIP tape serves as the primary air barrier across the wall field. Henry Air-Bloc fluid-applied air barrier at the underside of the concrete podium slab and all penetrations. Continue ZIP tape up and over the parapet, transitioning to Blueskin PE200HT high-temperature roof membrane at the roof level.
HVAC1 Bed: Ducted split heat pump; SEER2 17.5; HSPF2 9. 2 Bed: Ducted split heat pump; SEER2 17; HSPF2 9.
Duct SealingThe greater of 8 CFM/100 ft² conditioned floor area or 80 CFM
HVAC GradingFan Flow Test: N/A; Watt Draw Test: N/A; Refrigerant Charge: N/A
Mechanical VentilationERV; 84-90% rated recovery; Any Climate
Local Mechanical ExhaustBathroom(s): ≥50 CFM intermittent & ≤3.0 sones OR ≥20 CFM continuous & ≤2.0 sones. Kitchen(s): ≥100 CFM intermittent & ≤3.0 sones OR continuous ≥5 ACH & ≤1.0 sone. Both: Exhaust directly outdoors, ENERGY STAR certified, utilize ERV to meet these requirements.
ThermostatsProgrammable Thermostat
DHWElectric tank heater in unit (UEF ≥0.93)
DHW PipingSupply piping insulated to R-3 minimum; Max 1.8 gallons stored volume per run; Modeled pipe runs are optimized to 1/3 program default lengths.
Water FixturesWaterSense Certified Fixtures (Lavatory: ≤1.2 GPM, Shower: ≤2.0 GPM)
Refrigerator1 Bed: ≤422 kWh/yr; ENERGY STAR; Electric. 2 Bed: ≤489 kWh/yr; ENERGY STAR; Electric.
DishwasherAll: ≤240 kWh annual usage; ENERGY STAR; Electric
Clothes WasherIMEF 2.92; 105 kWh/yr; 4.5 cu ft; front-load; ENERGY STAR
Clothes DryerElectric standard vented dryer; CEF 3.94; moisture sensing
Stove / OvenInduction Stovetop & Convection Oven; Electric
Lighting100% high-efficacy (LED)
Solar ReadyDesignated Solar Zone ≥40% of total horizontal roof area; free of all obstructions; minimum 5 ft width; engineered for future 5 PSF collateral dead load; conduit pathways from roof to electrical service; labeled breaker space reserved in main panel.
EV ReadyEV Ready infrastructure for ≥20% of total parking. ≥10% with Active Level 2 EVSE (≥6.2 kVA / 30A at 208/240V per space). Remaining required spaces as Level 2 Ready branch circuits. EMS option: 2.1 kVA per space.
HPWH ReadyN/A
Paperwork & ModelingWUFI & HERS/ERI Energy model, 2021 IECC checklists, ENERGY STAR MFNC checklists, PHIUS checklists, PHIUS Feasibility Study, and incentive documentation.
Testing & VerificationWhole Building & Unit Blower Door Test, Mechanical Ventilation Testing, Room Balancing, Slab, Predrywall & Final Inspection.

Exterior Wall Assembly

Exterior Wall Assembly

Rim Joist

Rim Joist Assembly

Roof

Roof Assembly

Podium Option 1

Podium Option 1

Podium Option 2

Podium Option 2

Path Comparison - Incentives

All Paths: $175,000

  • MassSave Passive House Feasibility Study ($5,000): Rebate for completing a PHIUS feasibility study and a 1-hour charette with the design team and MassSave representative before construction is complete. Paid as a check within 4 months of the charette. IMPORTANT: Capped at 100% of the applicable service charge.
  • MassSave Passive House Energy Model ($20,000): Rebate for completing a PHIUS energy model and a 1-hour charette with the design team and MassSave representative before construction is complete. Paid as a check within 4 months of the meeting. IMPORTANT: Capped at 75% of the applicable service charge.
  • MassSave Passive House Pre-Certification ($30,000): Rebate for achieving PHIUS pre-certification toward the end of the pre-construction phase. Paid as a check within 4 months of pre-certification paperwork being provided to MassSave.
  • MassSave Passive House Certification ($120,000): Rebate for achieving PHIUS certification at the end of construction around certificate of occupancy. Paid as a check within 4 months of certification paperwork being provided to MassSave.
  • DOER Alternative Energy Credits (N/A - Ducted Systems Do Not Qualify): IMPORTANT: Although an estimate is provided where applicable, this incentive can vary widely between $300-1,500 per heat pump based on expected kWh usage and market value of alternative energy credits when sold.

Path Comparison - Net Cost Summary

PathTotal Cost $/sfTotal Incentives $/sfNet $/sfOpEx Factor
Path A$45.57$2.70$44.061.03
Path B (Recommended)$43.27$2.70$42.221.04
Path C$46.78$2.70$46.171.05

Path Comparison - Envelope

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
Exterior WallsPath AR-12.6 - 3" ROCKWOOL Comfortboard 80 CI secured with Technoform Thermal Isolator Clips & R-21 batt in cavity$3.85$0.00$3.850.85
Exterior WallsPath BR-12.6 - 2.5" ZIP System Insulated R-Sheathing & R-21 batt in cavity$3.50$0.00$3.500.95
Exterior WallsPath CR-12.6 - 3" ROCKWOOL Comfortboard 80 CI secured with Technoform Thermal Isolator Clips (no cavity batt)$3.40$0.00$3.400.85
Floor Over GaragePath ASteel Frame Slab: R-38 batt on thermally broken drop ceiling; Post Tensioned Slab: R-30 CI on either side of slab.$3.45$0.00$3.450.90
Floor Over GaragePath BSame as Path A$3.45$0.00$3.450.90
Floor Over GaragePath CSame as Path A$3.45$0.00$3.450.90
Rim JoistsPath AMinimum 3" closed-cell spray foam; CI continues over floor transitions without interruption.$0.10$0.00$0.100.85
Rim JoistsPath BSame as Path A$0.10$0.00$0.100.85
Rim JoistsPath CSame as Path A$0.10$0.00$0.100.85
RoofPath A11" Rigid Polyiso CI (R-60) in multiple layers with staggered joints$4.40$0.00$4.400.95
RoofPath BSame as Path A$4.40$0.00$4.400.95
RoofPath C9" Rigid Polyiso CI (R-50) in multiple layers with staggered joints$3.85$0.00$3.850.98
WindowsPath AWeighted Avg: U-0.15 / SHGC 0.20$6.25$0.00$6.251.05
WindowsPath BSame as Path A$6.25$0.00$6.251.05
WindowsPath CSame as Path A$6.25$0.00$6.251.05
DoorsPath AGlazed: U-0.15 / SHGC 0.20; Opaque: U-0.21 (R-4.75)$0.95$0.00$0.951.00
DoorsPath BSame as Path A$0.95$0.00$0.951.00
DoorsPath CSame as Path A$0.95$0.00$0.951.00
Air SealingPath AUnits: ≤0.30 CFM50/ft²; Whole Building: ≤0.06 CFM50/ft². Henry Blueskin VP100 self-adhered membrane across full exterior wall surface; Henry Air-Bloc fluid-applied at podium slab; VP100 sill pans and jamb wraps at windows/doors.$5.80$0.00$5.800.85
Air SealingPath BUnits: ≤0.30 CFM50/sqft; Whole Building: ≤0.06 CFM50/sqft. Henry Air-Bloc at podium slab; ZIP tape as primary wall air barrier; Blueskin PE200HT at roof; VP100 sill pans and jamb wraps at windows/doors.$3.85$0.00$3.851.05
Air SealingPath CSame as Path A (VP100 wall air barrier)$5.80$0.00$5.800.85

Path Comparison - Mechanical

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
HVACPath A1 Bed: Ducted split heat pump; SEER2 17.5; HSPF2 9. 2 Bed: Ducted split heat pump; SEER2 17; HSPF2 9.$6.60$0.00$6.601.10
HVACPath BSame as Path A$6.60$0.00$6.601.15
HVACPath CSame as Path A$6.60$0.00$6.601.15
Duct SealingPath AThe greater of 8 CFM/100 ft² conditioned floor area or 80 CFM$0.35$0.00$0.350.95
Duct SealingPath BSame as Path A$0.35$0.00$0.350.95
Duct SealingPath CSame as Path A$0.35$0.00$0.350.95
HVAC GradingPath AFan Flow Test: N/A; Watt Draw Test: N/A; Refrigerant Charge: N/A$0.00$0.00$0.001.00
HVAC GradingPath BSame as Path A$0.00$0.00$0.001.00
HVAC GradingPath CSame as Path A$0.00$0.00$0.001.00
Mechanical VentilationPath AERV; 84-90% rated recovery; Any Climate$4.40$0.00$4.401.30
Mechanical VentilationPath BSame as Path A$4.40$0.00$4.401.30
Mechanical VentilationPath CSame as Path A$4.40$0.00$4.401.30
Local Mechanical ExhaustPath ABathroom(s): ≥50 CFM intermittent & ≤3.0 sones OR ≥20 CFM continuous & ≤2.0 sones. Kitchen(s): ≥100 CFM intermittent & ≤3.0 sones OR continuous ≥5 ACH & ≤1.0 sone. Both: Exhaust directly outdoors, ENERGY STAR certified, utilize ERV.$0.30$0.00$0.301.10
Local Mechanical ExhaustPath BSame as Path A$0.30$0.00$0.301.10
Local Mechanical ExhaustPath CSame as Path A$0.30$0.00$0.301.10
ThermostatsPath AProgrammable Thermostat$0.09$0.00$0.091.05
ThermostatsPath BSame as Path A$0.09$0.00$0.091.05
ThermostatsPath CSame as Path A$0.09$0.00$0.091.05

Path Comparison - Plumbing & Appliances

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
DHWPath AElectric tank heater in unit (UEF ≥0.93)$1.15$0.00$1.150.90
DHWPath BSame as Path A$1.15$0.00$1.150.90
DHWPath C1 Bed: HPWH In Unit OR Corridor (UEF ≥3.45; 50 Gal). 2 Bed: HPWH In Unit OR Corridor (UEF ≥3.45; 66 Gal).$3.40$0.00$3.401.35
DHW PipingPath ASupply piping insulated to R-3 minimum; Max 1.8 gallons stored volume per run; Modeled pipe runs at 1/3 program default lengths.$1.50$0.00$1.500.95
DHW PipingPath BSame as Path A$1.50$0.00$1.500.95
DHW PipingPath CSame as Path A$1.50$0.00$1.500.95
Water FixturesPath AWaterSense Certified (Lavatory: ≤1.2 GPM, Shower: ≤2.0 GPM)$0.18$0.00$0.181.05
Water FixturesPath BSame as Path A$0.18$0.00$0.181.05
Water FixturesPath CSame as Path A$0.18$0.00$0.181.05
RefrigeratorPath A1 Bed: ≤422 kWh/yr; ENERGY STAR; Electric. 2 Bed: ≤489 kWh/yr; ENERGY STAR; Electric.$0.49$0.00$0.491.00
RefrigeratorPath BSame as Path A$0.49$0.00$0.491.00
RefrigeratorPath CAll: ≤550 kWh/yr; ENERGY STAR; Electric.$0.45$0.00$0.451.00
DishwasherPath AAll: ≤240 kWh/yr; ENERGY STAR; Electric$0.31$0.00$0.311.00
DishwasherPath BSame as Path A$0.31$0.00$0.311.00
DishwasherPath CSame as Path A$0.31$0.00$0.311.00
Clothes WasherPath AIMEF 2.92; 105 kWh/yr; 4.5 cu ft; front-load; ENERGY STAR$0.43$0.00$0.431.15
Clothes WasherPath BSame as Path A$0.43$0.00$0.431.15
Clothes WasherPath CSame as Path A$0.43$0.00$0.431.15
Clothes DryerPath AElectric standard vented dryer; CEF 3.94; moisture sensing$0.37$0.00$0.371.40
Clothes DryerPath BSame as Path A$0.37$0.00$0.371.40
Clothes DryerPath CSame as Path A$0.37$0.00$0.371.40
Stove / OvenPath AInduction Stovetop & Convection Oven; Electric$0.62$0.00$0.621.25
Stove / OvenPath BSame as Path A$0.62$0.00$0.621.25
Stove / OvenPath CSame as Path A$0.62$0.00$0.621.25

Path Comparison - Electrical

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
LightingPath A100% high-efficacy (LED)$1.05$0.00$1.050.80
LightingPath BSame as Path A$1.05$0.00$1.050.80
LightingPath CSame as Path A$1.05$0.00$1.050.80
Solar ReadyPath AContiguous zone ≥40% of total horizontal roof area; free of obstructions; minimum 5 ft width; engineered for 5 PSF future dead load; conduit pathways from roof to electrical service; labeled breaker space reserved.$0.15$0.00$0.151.00
Solar ReadyPath BSame as Path A$0.15$0.00$0.151.00
Solar ReadyPath CSame as Path A$0.15$0.00$0.151.00
EV ReadyPath AEV Ready for ≥20% of parking; ≥10% with Active Level 2 EVSE (≥6.2 kVA per space); remaining spaces as Level 2 Ready branch circuits; EMS option at 2.1 kVA per space.$0.31$0.00$0.311.30
EV ReadyPath BSame as Path A$0.31$0.00$0.311.30
EV ReadyPath CSame as Path A$0.31$0.00$0.311.30
HPWH ReadyPath AN/A$0.00$0.00$0.001.00
HPWH ReadyPath BSame as Path A$0.00$0.00$0.001.00
HPWH ReadyPath CSame as Path A$0.00$0.00$0.001.00

Path Comparison - Soft Costs

ItemPathDetailed SpecificationsCost $/sfIncentive $/sfNet $/sfOpEx Factor
Paperwork & ModelingPath AWUFI & HERS/ERI Energy model, 2021 IECC checklists, ENERGY STAR MFNC checklists, PHIUS checklists, PHIUS Feasibility Study, and incentive documentation.$1.69$0.85$0.851.00
Paperwork & ModelingPath BSame as Path A$1.69$0.85$0.851.00
Paperwork & ModelingPath CSame as Path A$1.69$0.85$0.851.00
Testing & VerificationPath AWhole Building & Unit Blower Door Test, Mechanical Ventilation Testing, Room Balancing, Slab, Predrywall & Final Inspection.$0.77$1.85-$1.081.00
Testing & VerificationPath BSame as Path A$0.77$1.85-$1.081.00
Testing & VerificationPath CSame as Path A$0.77$1.85-$1.081.00

Additional Design Considerations Not Represented In This Study

N/A